HE1.5XINH

  • icon Summary
  • icon Options
  • icon Drawings
  • icon Literature
  • icon Accessories
HE1.5XINH

SPECIFICATIONS

Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range: 375-1,575 CFM
AHRI 1060 Certified Core: One L62-G5 and one L125-G5
Standard Features:
Non-fused disconnect
24 VAC transformer/relay package
Filters:
Total qty. 4, MERV 8: (2) 14" x 20" x 2" and (2) 16" x 20" x 2"
Unit Dimensions & Weight:
53 1/4" L x 34 1/2" W x 53 3/4" H
337-464 lbs., varies by option(s)
Max. Shipping Dimensions & Weight (on pallet):
70" L x 47" W x 53" H
530 lbs.
Motor(s):
Qty. 2, 1.0 HP ea., Direct drive standard motorized impeller packages
HE1.5XINH

OPTIONS


  • Qty. 2, EC Motor (see HE1.5XINH EC Motor submittal) -
    • 1.0 HP 120V/1Ph/60HZ,
    • 1.0 HP 208-230V/1Ph/60HZ
  • Integrated programmable controls
  • Fused disconnect
  • Double wall construction
  • Gravity backdraft dampers
  • Motorized isolation dampers - OA, EA or both airstreams
  • Qty. 2, Factory mounted filter alarms
  • Independent blower control
  • Exterior paint - white, custom colors
  • Bypass economizer (see bypass DIM drawing) -
    • dry-bulb temperature controls (standard),
    • enthalpy controls (option)
HE1.5XINH

LITERATURE


Installation and Operation Manual Update: Please note typographical error in French translation regarding installation of Solid State Speed Controllers. English warning is correct. French Translations have now been corrected as of 03/15/16.

Correction of French translation

HE1.5XINH

ACCESSORIES


  • Filters - MERV 13, 2" (shipped loose)
  • Backdraft damper - OA or EA
  • Digital time clock - wall mount (TC7D-W), in exterior enclosure (TC7D-E)
  • Motion occupancy control - ceiling mount (MC-C), wall mount (MC-W)
  • Carbon dioxide control - wall mount (CO2-W), duct mount (CO2-D)
  • Electric duct heater - EK series (1–60 kW)
  • Indirect gas-fired duct furnace - GH series (50-400 MBH), installed downstream of any fans